Transformer kVA Sizing Calculator

Enter your load current and system voltage — get the required kVA and the next standard three-phase or single-phase transformer size, with growth margin applied.

Calculator

Load current to transformer size

Planning aid only. Rounds your connected load (plus growth margin) up to the next standard rating — it does not apply the 125% continuous factor or a full Article 220 load calculation. Confirm the final selection with your engineer or spec.

How it works

The math behind the result

Three-phase
kVA = V × I × 1.732 ÷ 1000
Single-phase
kVA = V × I ÷ 1000
Growth margin
Required kVA = connected load × (1 + margin). Size to the next standard rating at or above the result.
Standard three-phase sizes
15 · 30 · 45 · 75 · 112.5 · 150 · 225 · 300 · 500 · 750 · 1000 · 1500 · 2000 · 2500 · 3000 · 3750 · 5000kVA
Standard single-phase sizes
5 · 10 · 15 · 25 · 37.5 · 50 · 75 · 100 · 167 · 250 · 333kVA
Why kVA, not kW
Transformers are rated in kVA because heating depends on current and voltage, not power factor. kVA = kW ÷ PF — a 0.85 PF load pulls more current per kW.
FAQ

Common questions

How do you calculate transformer kVA from load current?
For a three-phase load, kVA = voltage × current × 1.732 ÷ 1000. For a single-phase load, kVA = voltage × current ÷ 1000. Enter your load current and system voltage and the calculator does both, then applies any growth margin you specify.
What are the standard transformer sizes?
Common three-phase distribution sizes run 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, and 5000kVA. Single-phase sizes run 5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, and 333kVA. The calculator rounds your load up to the next standard size.
How much headroom should I add for future load growth?
A common practice is 20–25% spare capacity for commercial service equipment, but the right margin depends on your load mix, diversity, and expansion plans. Continuous loads require sizing at 125% per the Article 220 load calculation — this tool does not apply that factor automatically, so include it in your load or growth margin; overcurrent protection per 450.3 is a separate step — confirm with your engineer.
Does kVA depend on power factor?
No — kVA is independent of power factor, which is why transformers are rated in kVA. Power factor matters for real power (kW = kVA × PF) and for current draw of a fixed kW load: a lower PF pulls more current for the same kW.
Can you quote the transformer this calculator recommends?