Mixed THHN or XHHW fills in EMT, IMC, RMC, or PVC — checked against the NEC Chapter 9 limits: 53% for one conductor, 31% for two, 40% for three or more.
Bare equipment grounding conductor (optional) — area per Chapter 9 Table 8, added to the fill and conductor count.
Areas per NEC Chapter 9 Tables 4 and 5 (2023 basis). Compact-stranded conductors are smaller than tabulated. Ampacity adjustment (310.15) is a separate check. Nipples 24" or shorter are permitted 60% fill (Table 1) — not modeled here. Quick-reference only — a licensed engineer dictates final values and confirms against the adopted NEC.